Introduction
This Guidance expands on the information given in Advice
Sheet 9: Electricity at Work, in which a regime of User Checks, Formal
Visual Inspection, and Test and Examination is outlined.
Further information is given below on carrying out User Checks and Formal
Visual Inspection as well as documentation and reporting.
With regard to Test and Examination of the Installation and Appliances,
you should consult a competent electrician to advise on frequency and
necessity.
Documentation and Reporting
The results of the inspections should be formally recorded for each piece
of equipment, which should be uniquely identified, in addition to the
following items as a minimum standard:
1. The location of the equipment
2. The Environment in which the equipment is used and tested
3. The date of the inspection/test
4. Any maintenance carried out
5. The name of the competent person who conducted the inspection/tests
6. The items inspected/tested and the condition
7. Next inspection date
An Inspection Log sheet has been provided for this purpose.
The appropriate manager or supervisor should be advised promptly of any
safety deficiencies revealed during the inspections (and tests if carried
out). It is the manager's responsibility to ensure that equipment cannot
be energised or used whilst in a potentially hazardous condition. In the
absence of the manager the equipment should be taken out of operation
until repaired/made safe.
back
to the top
Frequency of Checks and Inspections
The time between inspections needs to be adjusted to suit the conditions
of use and the likelihood of damage that may cause a hazard, e.g. earthed
equipment (kettles, some floor cleaners, etc) should be inspected every
6 months to 1 year; Hand held double insulated equipment (some floor cleaners,
hair dryers) every 6 months to 1 year; Computers, photocopiers, double
insulated fans, table lamps, etc every 2 to 4 years. Leads and plugs to
the above, and mains extension leads should be inspected every 6 months
to 4 years depending on the type of equipment it is connected to.
Staff should be aware of the need for good housekeeping and supervisors
should arrange that this is checked frequently to encourage good practice.
Equipment should be inspected immediately following any movement to a
new location and if the inspection indicates any possibility of damage
the equipment should be tested.
Equipment is a harsher environment, or where the supply cord is exposed
to strain or damage, or where the equipment is moved may require more
frequent inspection and possibly testing. In some cases constant vigilance
is required, e.g. for calculators, laptop computers and associated battery
eliminators that are much more likely to be damaged owing to frequent
transportation, connection and disconnection.
back
to the top
1. DAILY USER CHECKS
Check that the equipment is installed and operated in accordance with
the manufacturer's instructions. Notwithstanding the manufacturer's instructions,
the following are examples of items that should be checked:
-
Cables are not located where they may be trodden on or snagged;
-
Means of disconnection/isolation from the mains supply are readily
accessible;
-
Space around the equipment is adequate for ventilation and cooling
and equipment ventilation openings are not blocked by documents, media
etc;
-
Liquids and dust/solids are not placed where they may spill into
the equipment;
-
Equipment is not positioned so close to walls and partitions that
the cord is forced into a tight bend as it exits the equipment (this
may also indicate inadequate spacing ventilation and cooling);
-
equipment is operated with covers in place and enclosure doors closed.
2. FORMAL VISUAL INSPECTION
The inspection of the equipment should be preceded by a User Check -
see section 1.
Pluggable Equipment
Pluggable equipment should be disconnected to enable a safe and thorough
inspection of the equipment and power cords. The following procedure should
be observed.
1. Ensure that the equipment can be taken out of service without causing
disruption;
2. Power down the equipment in accordance with the manufacturer's instructions
and any local operating instructions;
3. Unplug external signal connections
4. Unplug the mains supply, or if the equipment is supplied via an uninterruptable
power supply (UPS), unplug the equipment from the UPS.
back
to the top
Permanently connected equipment
Where the equipment is permanently connected to the mains supply (i.e.
not via a plug) there are two possible situations:
1. The equipment is stationary and there is no flexible mains cable subject
to movement, stress or damage and the mains terminals are not subject
to vibration: in this case it will not usually be necessary to disconnect
the equipment prior to inspection, but isolation is advised.
2. For other permanently connected equipment the manufacturer's guidance
should be sought.
back
to the top
Inspection procedure
1. With all covers in place the exterior of the equipment should be inspected
for:
Particular attention should be paid to possible physical damage to accessible
mains components such as switches, fuses and equipment couplers.
2. All mains power cords, including interconnecting cords, should be
checked for physical damage and if necessary repaired or replaced by a
competent service engineer/electrician.
3. Where rewirable plugs or equipment couplers are used their covers
should be removed and: (See Fig.1)
-
The termination and cord grips should be checked for tightness and
alignment (the outer sheath of a cable should be seen at both sides
of a cord grip and the insulation should be present up to each termination).
-
The terminations should be checked for correct polarity;
-
The conductors should be checked for damaged or loose strands.
4. Operator-accessible fuses on the outside of the equipment should be
checked for the correct type and rating. If the equipment manufacturer
has specified a particular rating for the plug fuse, this should also
be checked. If the manufacturer has not specified a particular rating
for the plug, the preferred
fuse size, related to the cross-sectional area of the cord conductors,
is given in Table 1.
back
to the top
| Table 1: Cord conductors and plug fuses |
| Conductor Size |
0.5mm |
0.75mm |
1.0mm |
1.25mm or 1.5mm |
Recommended Fuse (BS 1363 Part 3) |
3 amp |
5 amp |
10 amp |
13 amp |
1) Optical fibre interconnections Some equipment use optical fibre interconnections.
The sources driving these vary in power and some can cause eye damage.
From the outside there is nothing to distinguish a fibre optic cable from
an electrical cable. Equipment employing certain classes of laser is required
to be labelled. However, the equipment manufacturer's advice should be
followed at all times. Do not disconnect fibre optic cables unless this
required by the manufacturers instructions. Finally, under no circumstances
look directly into the end of a fibre optic cable or connector; the radiation
used is often not visible but this does not mean it cannot cause eye damage.
(2) Uninterruptable power supplies (UPS) These recommendations are not
intended to apply to uninterruptable power supplies (UPS). Remember that
a UPS will maintain mains voltage at its output after it has been disconnected
from the mains supply. Before checking or testing a UPS advice should
be sought from its manufacturer.
back
to the top
Supplementary
Advice: User Checks and Formal Visual Inspection
A copy of this supplementary advice sheet is available to download in
the following formats:
Supplementary
Advice: User Checks and Formal Visual Inspection - MS
Word format 61Kb
Supplementary
Advice: User Checks and Formal Visual Inspection - PDF format 74Kb
Supplementary
Advice: User Checks and Formal Visual Inspection - Plain
Text format 175Kb 
To view and print PDF files, you must have
Adobe® Acrobat® Reader installed.
Link on the Adobe logo to download the software.

Adobe Acrobat documents can be converted back to
plain text using Adobe's Web-based conversion service. |
|
To view and print Microsoft Word files, you must
either have Microsoft Word installed on your computer, or you can download
free Microsoft Word Viewer software.
Link on the logo to download the software

|
|